Skip to main content

ENG-C444-001.351-1 - Procedure V1

Major VersionM

by Petr Roupec

Introduction

This example is describing how to create a notification of trip for GT11 at Panglima power station. This notification will detect drop of turbine power under 5MW and set a flag of "GT11 no power". The change of flag will trigger a notification script.

How does it works

For E-PMS notification system method of status flags has been chosen. The E-PMS Notification System is Designed as follows:

  1. For monitored process value event is defined
  2. Activation of the Event set a digital tag representing its status
  3. Change od status is triggering notification script

EVENT_TG2_GT11_POWER_LOST - Event triggered by the tag 11MBY10CE901&XQ01 going below certain level

STATUS_TG2_GT11_NO_POWER - STATUS flag set by the EVENT_TG2_GT11_POWER_LOST and stays set until conditions of event are present

NOTIFICATION_TG2_GT11_NO_POWER - NOTIFICATION script is called once STATUS change is detected

  1. Open the "Device Manager" at Reliance SCADA system Open the "Device Manager" at Reliance SCADA system
    • Open the "Device Manager" at Reliance SCADA system

  2. Add an event called:  EVENT_TG2_GT11_POWER_LOST Define EVENT parameters
    • Add an event called: EVENT_TG2_GT11_POWER_LOST

    • Define EVENT parameters

    • Tag Name

    • Event description

    • Process tag which is being evaluated

    • Type of evaluation and range of the values

  3. Define Status Flag STATUS_TG2_GT11_NO_POWER Tag name
    • Define Status Flag STATUS_TG2_GT11_NO_POWER

    • Tag name

    • Bool type

    • Visibility on OPC UA server

  4. Set STATUS flag  STATUS_TG2_GT11_NO_POWER  by the event
    • Set STATUS flag STATUS_TG2_GT11_NO_POWER by the event

  5. Open Script Manager in order to add email notification script Open Script Manager in order to add email notification script
    • Open Script Manager in order to add email notification script

  6. Script is triggered by the change of Status Flag  STATUS_TG2_GT11_NO_POWER
    • Script is triggered by the change of Status Flag STATUS_TG2_GT11_NO_POWER

    • Please note that errors in the scripts will stop it's executions

Finish Line