Introduction
This example is describing how to create a notification of trip for GT11 at Panglima power station. This notification will detect drop of turbine power under 5MW and set a flag of "GT11 no power". The change of flag will trigger a notification script.
How does it works
For E-PMS notification system method of status flags has been chosen. The E-PMS Notification System is Designed as follows:
- For monitored process value event is defined
- Activation of the Event set a digital tag representing its status
- Change od status is triggering notification script
EVENT_TG2_GT11_POWER_LOST - Event triggered by the tag 11MBY10CE901&XQ01 going below certain level
STATUS_TG2_GT11_NO_POWER - STATUS flag set by the EVENT_TG2_GT11_POWER_LOST and stays set until conditions of event are present
NOTIFICATION_TG2_GT11_NO_POWER - NOTIFICATION script is called once STATUS change is detected
-
-
Open the "Device Manager" at Reliance SCADA system
-
-
-
Add an event called: EVENT_TG2_GT11_POWER_LOST
-
Define EVENT parameters
-
Tag Name
-
Event description
-
Process tag which is being evaluated
-
Type of evaluation and range of the values
-
-
-
Define Status Flag STATUS_TG2_GT11_NO_POWER
-
Tag name
-
Bool type
-
Visibility on OPC UA server
-
-
-
Set STATUS flag STATUS_TG2_GT11_NO_POWER by the event
-
-
-
Open Script Manager in order to add email notification script
-
-
-
Script is triggered by the change of Status Flag STATUS_TG2_GT11_NO_POWER
-
Please note that errors in the scripts will stop it's executions
-